SHENGLONG’S INDEPENDENTLY DEVELOPED iPANEL PLATFORM
iPanel-E Low-Voltage Switchgear
Shenglong’s optimised low-voltage switchgear series for power distribution and motor control, bringing modular cabinet construction together with local monitoring and connected operating information.
Developed through improvements to the iPanel-L platform, iPanel-E combines electrical performance, configurable intelligence, and project-focused equipment selection.
Main busbar configurations reach 6300 A at 50 Hz. We coordinate electrical ratings, cabinet arrangements, protection, and digital functions around your application.

Practical Structure and Front Maintenance
iPanel-E simplifies and optimises the iPanel-L structure. Its cabinet construction is closer to conventional GCS and MNS-L arrangements, while retaining the iPanel family appearance and Shenglong’s iDrip system. It is a cost-conscious choice rather than a direct replacement for every structural feature of iPanel-L.
Fixed and withdrawable arrangements are available. Front cabling and maintenance can be configured for near-wall installation. This arrangement requires increased cabinet width. Confirm the complete cabinet dimensions, cable space, wall clearance, and ventilation in the project drawings.
Independently Assessed Electrical Performance
iPanel-E configurations have supporting IECEE CB Scheme, TÜV Rheinland conformity, and CQC certification documentation. We provide the applicable documents for your selected equipment and project submission.
Electrical Assembly Verification
Supporting documentation covers IEC 61439-1/-2:2020 configurations, including dielectric performance, temperature rise, short-circuit withstand, protective circuits, and mechanical operation.
Internal-Arcing Performance
A 400 V, 6300 A configuration has been assessed at an arcing test current of 135 kA for 1 second, arcing class C, with Form 4b separation. The tested construction and installation conditions are coordinated with the project.
Verification applies to the corresponding equipment and test conditions. Internal-arcing performance is separate from rated short-time withstand. EU declarations and marking are addressed for the equipment supplied where applicable.
Design FeaturesTypical ApplicationsTechnical DataCabinet OptionsMonitoringSpecial ApplicationsiPanel Family
An Optimised Platform for Distribution and Monitoring
Modular Cabinet Engineering
A 25 mm mounting pitch supports standardised arrangements for distribution, motor control, and compensation. Cabinet function, circuit loading, separation, and cable space are selected together.
Fixed and Withdrawable Arrangements
Select fixed equipment, withdrawable devices, or modular drawer circuits to match the required operating and maintenance strategy.
Local Operating Information
A selected local touchscreen brings incoming electrical measurements, switch status, energy, alarms, and temperature data into one interface, reducing the need to inspect instruments individually.
Scalable Digital Scope
Local monitoring can be extended to supervisory communication, data storage, energy reporting, and user management. Functions are selected for the project’s operating needs and investment scope.
Typical Applications
Manufacturing and Motor Control
Distribution and motor circuits for production equipment and plant utilities, with starting methods, protection, maintenance, and circuit quantities selected for the process.
Commercial, Healthcare, and Education
Building distribution and monitoring for commercial developments, hospitals, and campuses, with operating information organised for the maintenance team.
Power and Industrial Facilities
Incoming, outgoing, and auxiliary circuits in power and industrial installations, matched to the load, fault duty, and environment.
Projects Requiring Connected Operation
Installations seeking local electrical visibility, alarm information, energy reporting, and integration with a supervisory platform.
Technical Specifications
The following ranges cover the selected verified configurations. Final values are established for each cabinet function and electrical arrangement.
| Parameter | Specification |
|---|---|
| Application | Power distribution and motor control |
| Installation | Indoor |
| Operational voltage options | 127 / 208 / 220 / 380 / 400 V AC; 415 / 440 / 460 / 480 / 500 / 540 / 660 / 690 V AC, depending on configuration |
| Rated frequency | 50/60 Hz |
| Main busbar rated current | 4000–6300 A at 50 Hz for the selected verified configurations |
| Main busbar current at 60 Hz | 95% of the corresponding 50 Hz rating; up to 5985 A for the corresponding 6300 A configuration |
| Feeder cabinet distribution busbar current | 1900–4200 A at 50 Hz for the selected verified configurations; frequency-dependent |
| Outgoing control cabinet distribution busbar current | 400–2100 A at 50 Hz for the selected verified configurations; confirm the applicable 60 Hz rating separately |
| Rated insulation voltage | Up to 1000 V; confirm the value for each cabinet type |
| Enclosure protection options | IP30 / IP31 / IP32 / IP40 / IP41 / IP42 / IP43 / IP44 |
| Mechanical impact rating | IK10 according to the selected construction |
Short-Time Withstand Ratings by Voltage Group
| Operational Voltage Group | Main Busbar Icw | Distribution Busbar Icw |
|---|---|---|
| 127 / 208 / 220 / 380 / 400 V AC | 135 kA / 1 s | 100 kA / 1 s |
| 415 / 440 / 460 / 480 / 500 / 540 / 660 / 690 V AC | 100 kA / 1 s | 85 kA / 1 s |
Rating selection: Voltage, rated current, withstand capability, enclosure protection, and thermal performance are coordinated in the project configuration. Busbar current is separate from individual outgoing-circuit current. Available current ratings depend on the selected cabinet construction and verified configuration.
Cabinet and Functional Options
Circuit-Breaker Cabinets
Incoming, outgoing, and bus-coupling duties with fixed or withdrawable devices. Main busbar configurations reach 6300 A at 50 Hz; device rating and enclosure dimensions are selected separately.
Feeder Cabinets
Fixed and withdrawable feeder arrangements, including circuit options up to 2000 A according to the selected construction.
Withdrawable Drawer Cabinets
Functional units for distribution and motor control, with circuit options up to 630 A. Unit size, equipment, loading, and cooling are selected together.
Reactive Power Compensation
Fixed compensation arrangements up to 480 kvar, with switching steps, capacitors, protection, and harmonic mitigation matched to the load.
| Parameter | Size Options |
|---|---|
| Frame mounting pitch | 25 mm |
| Cabinet height | 2200 mm |
| Cabinet widths | 600 / 800 / 1000 / 1200 mm, depending on cabinet type |
| Cabinet depths | 800 / 1000 mm |
| Main busbar location | Top or rear |
Available dimensions depend on cabinet function. High-current and high-withstand arrangements require their own equipment layout, thermal design, cable access, and project drawings.
Local Monitoring and Connected Operation
Standard iDrip Monitoring
Standard supply includes Shenglong’s iDrip monitoring system, with an English-language interface and Modbus RTU communication. The software version is matched to each iPanel series.
- Incoming cabinets: current, voltage, active and reactive power, energy, harmonics, and circuit-breaker open/closed status.
- Outgoing circuits: switch-status monitoring is normally provided. Harmonic monitoring is not part of the normal outgoing-circuit scope; any additional outgoing measurements are agreed in the project schedule.
- Remote switching: primarily provided for incoming air circuit breakers (ACBs), with the controlled circuits and interlocks defined in the project scheme. Remote operation of MCCBs or MCBs requires suitable motor operators, contactors, or corresponding control circuits.
Voice control, temperature monitoring, busbar temperature monitoring, and other additional modules are optional and require separate customer confirmation. The quotation identifies the data points, display arrangement, software functions, and controlled circuits.


Performance and Special Applications
Seismic Verification
Configurations have undergone seismic testing at intensity levels 8 and 9. Cabinet construction, installation anchorage, and site requirements are reviewed together.
Corrosion Resistance
An 1800-hour salt-spray test is documented for the tested samples. Enclosure treatment and site exposure are selected together; test duration is not a service-life prediction.
High-Altitude Insulation
Clearance, creepage, and dielectric verification includes a 5000 m altitude correction for the corresponding configuration. Thermal ratings and the complete site arrangement require separate review.
Electrical and Environmental Coordination
We review enclosure protection, heat dissipation, circuit loading, and service conditions together, rather than selecting individual maximum values in isolation.
Installation and Service Conditions
iPanel-E is intended for indoor installation at −5°C to +40°C, with a 24-hour average not exceeding +35°C. Higher temperatures, humidity, condensation risk, altitude, corrosion, and seismic requirements are addressed through the selected construction and ratings.
We provide project arrangement drawings covering cabinet combinations, cable access, ventilation, maintenance space, and connection interfaces.
iPanel-E Project References
Explore an iPanel-E application in automotive manufacturing.

AUTOMOTIVE MANUFACTURING · CHINA
BYD, Changzhou
Shenglong iPanel-E low-voltage switchgear is installed at a BYD site in Changzhou, Jiangsu.
Selecting Within the iPanel Family
iPanel-L
Elaborate cabinet and plug-in connection design, an independent busbar arrangement, and higher-protection options. Rear maintenance access is required.
iPanel-E
Simplified, cost-conscious construction with iPanel styling and iDrip monitoring. Wider front-access arrangements can support near-wall installation.
AI-iPanel
Compact feeder options, U-section busbars for selected high-current designs, and AI applications. The 500 mm feeder requires 3P devices; drawer circuits are recommended at 400 A or below.
iPanel-M
Shenglong’s medium-voltage platform, with its own construction, ratings, and verification. The low-voltage comparisons above do not apply to iPanel-M.
Circuit-Breaker Choice and Project Delivery
All three low-voltage iPanel series can accommodate mainstream circuit-breaker brands, including ABB, Siemens, Schneider Electric, and Shenglong, subject to the selected device dimensions and cabinet arrangement. Shenglong circuit breakers offer a cost-effective project option. For iPanel-L and iPanel-E, 3P or 4P devices do not by themselves impose the AI-iPanel 500 mm-width restriction.
English drawings and operation and maintenance manuals can be provided. Overseas on-site services are quoted separately, with the service scope agreed for the project.
Technical Documentation and Project Support
We support selection and project submissions with configuration information, applicable certification and test documentation, arrangement drawings, and installation requirements. Send your single-line diagram and equipment schedule to begin the review.
Plan Your Project with iPanel-E
- Location, application, quantities, and delivery schedule.
- Operational voltage, frequency, and earthing system.
- Main, distribution, and individual circuit current ratings.
- Short-circuit current, duration, and any internal-arcing requirements.
- Fixed or withdrawable units, internal separation, and enclosure protection.
- Local displays, measurements, alarms, protocols, and supervisory interfaces.
- Cabinet layout, connections, altitude, temperatures, and other site conditions.
If you are still planning your project, send the information you have. We can discuss the remaining details with you.
Prefer email? info@shenglong-hub.com
Ratings and functions apply to their respective configurations. The final equipment, software, documentation, and supply scope are established in the agreed project technical schedule.