iPanel-E

SHENGLONG’S INDEPENDENTLY DEVELOPED iPANEL PLATFORM

iPanel-E Low-Voltage Switchgear

Shenglong’s optimised low-voltage switchgear series for power distribution and motor control, bringing modular cabinet construction together with local monitoring and connected operating information.

Developed through improvements to the iPanel-L platform, iPanel-E combines electrical performance, configurable intelligence, and project-focused equipment selection.

Main busbar configurations reach 6300 A at 50 Hz. We coordinate electrical ratings, cabinet arrangements, protection, and digital functions around your application.

Discuss Your ProjectTechnical Specifications

Shenglong iPanel-E low-voltage switchgear lineup
Cabinet arrangements and installed equipment are selected for each project.

Practical Structure and Front Maintenance

iPanel-E simplifies and optimises the iPanel-L structure. Its cabinet construction is closer to conventional GCS and MNS-L arrangements, while retaining the iPanel family appearance and Shenglong’s iDrip system. It is a cost-conscious choice rather than a direct replacement for every structural feature of iPanel-L.

Fixed and withdrawable arrangements are available. Front cabling and maintenance can be configured for near-wall installation. This arrangement requires increased cabinet width. Confirm the complete cabinet dimensions, cable space, wall clearance, and ventilation in the project drawings.

Independently Assessed Electrical Performance

iPanel-E configurations have supporting IECEE CB Scheme, TÜV Rheinland conformity, and CQC certification documentation. We provide the applicable documents for your selected equipment and project submission.

Electrical Assembly Verification

Supporting documentation covers IEC 61439-1/-2:2020 configurations, including dielectric performance, temperature rise, short-circuit withstand, protective circuits, and mechanical operation.

Internal-Arcing Performance

A 400 V, 6300 A configuration has been assessed at an arcing test current of 135 kA for 1 second, arcing class C, with Form 4b separation. The tested construction and installation conditions are coordinated with the project.

Verification applies to the corresponding equipment and test conditions. Internal-arcing performance is separate from rated short-time withstand. EU declarations and marking are addressed for the equipment supplied where applicable.

Design FeaturesTypical ApplicationsTechnical DataCabinet OptionsMonitoringSpecial ApplicationsiPanel Family

An Optimised Platform for Distribution and Monitoring

Modular Cabinet Engineering

A 25 mm mounting pitch supports standardised arrangements for distribution, motor control, and compensation. Cabinet function, circuit loading, separation, and cable space are selected together.

Fixed and Withdrawable Arrangements

Select fixed equipment, withdrawable devices, or modular drawer circuits to match the required operating and maintenance strategy.

Local Operating Information

A selected local touchscreen brings incoming electrical measurements, switch status, energy, alarms, and temperature data into one interface, reducing the need to inspect instruments individually.

Scalable Digital Scope

Local monitoring can be extended to supervisory communication, data storage, energy reporting, and user management. Functions are selected for the project’s operating needs and investment scope.

Typical Applications

Manufacturing and Motor Control

Distribution and motor circuits for production equipment and plant utilities, with starting methods, protection, maintenance, and circuit quantities selected for the process.

Commercial, Healthcare, and Education

Building distribution and monitoring for commercial developments, hospitals, and campuses, with operating information organised for the maintenance team.

Power and Industrial Facilities

Incoming, outgoing, and auxiliary circuits in power and industrial installations, matched to the load, fault duty, and environment.

Projects Requiring Connected Operation

Installations seeking local electrical visibility, alarm information, energy reporting, and integration with a supervisory platform.

Technical Specifications

The following ranges cover the selected verified configurations. Final values are established for each cabinet function and electrical arrangement.

Parameter Specification
Application Power distribution and motor control
Installation Indoor
Operational voltage options 127 / 208 / 220 / 380 / 400 V AC; 415 / 440 / 460 / 480 / 500 / 540 / 660 / 690 V AC, depending on configuration
Rated frequency 50/60 Hz
Main busbar rated current 4000–6300 A at 50 Hz for the selected verified configurations
Main busbar current at 60 Hz 95% of the corresponding 50 Hz rating; up to 5985 A for the corresponding 6300 A configuration
Feeder cabinet distribution busbar current 1900–4200 A at 50 Hz for the selected verified configurations; frequency-dependent
Outgoing control cabinet distribution busbar current 400–2100 A at 50 Hz for the selected verified configurations; confirm the applicable 60 Hz rating separately
Rated insulation voltage Up to 1000 V; confirm the value for each cabinet type
Enclosure protection options IP30 / IP31 / IP32 / IP40 / IP41 / IP42 / IP43 / IP44
Mechanical impact rating IK10 according to the selected construction

Short-Time Withstand Ratings by Voltage Group

Operational Voltage Group Main Busbar Icw Distribution Busbar Icw
127 / 208 / 220 / 380 / 400 V AC 135 kA / 1 s 100 kA / 1 s
415 / 440 / 460 / 480 / 500 / 540 / 660 / 690 V AC 100 kA / 1 s 85 kA / 1 s

Rating selection: Voltage, rated current, withstand capability, enclosure protection, and thermal performance are coordinated in the project configuration. Busbar current is separate from individual outgoing-circuit current. Available current ratings depend on the selected cabinet construction and verified configuration.

Cabinet and Functional Options

Circuit-Breaker Cabinets

Incoming, outgoing, and bus-coupling duties with fixed or withdrawable devices. Main busbar configurations reach 6300 A at 50 Hz; device rating and enclosure dimensions are selected separately.

Feeder Cabinets

Fixed and withdrawable feeder arrangements, including circuit options up to 2000 A according to the selected construction.

Withdrawable Drawer Cabinets

Functional units for distribution and motor control, with circuit options up to 630 A. Unit size, equipment, loading, and cooling are selected together.

Reactive Power Compensation

Fixed compensation arrangements up to 480 kvar, with switching steps, capacitors, protection, and harmonic mitigation matched to the load.

Parameter Size Options
Frame mounting pitch 25 mm
Cabinet height 2200 mm
Cabinet widths 600 / 800 / 1000 / 1200 mm, depending on cabinet type
Cabinet depths 800 / 1000 mm
Main busbar location Top or rear

Available dimensions depend on cabinet function. High-current and high-withstand arrangements require their own equipment layout, thermal design, cable access, and project drawings.

Local Monitoring and Connected Operation

Standard iDrip Monitoring

Standard supply includes Shenglong’s iDrip monitoring system, with an English-language interface and Modbus RTU communication. The software version is matched to each iPanel series.

  • Incoming cabinets: current, voltage, active and reactive power, energy, harmonics, and circuit-breaker open/closed status.
  • Outgoing circuits: switch-status monitoring is normally provided. Harmonic monitoring is not part of the normal outgoing-circuit scope; any additional outgoing measurements are agreed in the project schedule.
  • Remote switching: primarily provided for incoming air circuit breakers (ACBs), with the controlled circuits and interlocks defined in the project scheme. Remote operation of MCCBs or MCBs requires suitable motor operators, contactors, or corresponding control circuits.

Voice control, temperature monitoring, busbar temperature monitoring, and other additional modules are optional and require separate customer confirmation. The quotation identifies the data points, display arrangement, software functions, and controlled circuits.

Illustrative iPanel-E local monitoring display
Illustrative interface. Display language and data points are specified for the project.
iPanel-E meters and sensors connected to a supervisory system
Illustrative connected-system architecture.

Performance and Special Applications

Seismic Verification

Configurations have undergone seismic testing at intensity levels 8 and 9. Cabinet construction, installation anchorage, and site requirements are reviewed together.

Corrosion Resistance

An 1800-hour salt-spray test is documented for the tested samples. Enclosure treatment and site exposure are selected together; test duration is not a service-life prediction.

High-Altitude Insulation

Clearance, creepage, and dielectric verification includes a 5000 m altitude correction for the corresponding configuration. Thermal ratings and the complete site arrangement require separate review.

Electrical and Environmental Coordination

We review enclosure protection, heat dissipation, circuit loading, and service conditions together, rather than selecting individual maximum values in isolation.

Installation and Service Conditions

iPanel-E is intended for indoor installation at −5°C to +40°C, with a 24-hour average not exceeding +35°C. Higher temperatures, humidity, condensation risk, altitude, corrosion, and seismic requirements are addressed through the selected construction and ratings.

We provide project arrangement drawings covering cabinet combinations, cable access, ventilation, maintenance space, and connection interfaces.

iPanel-E Project References

Explore an iPanel-E application in automotive manufacturing.

Shenglong iPanel-E switchgear at the BYD site in Changzhou

AUTOMOTIVE MANUFACTURING · CHINA

BYD, Changzhou

Shenglong iPanel-E low-voltage switchgear is installed at a BYD site in Changzhou, Jiangsu.

View Project Reference →

Selecting Within the iPanel Family

iPanel-L

Elaborate cabinet and plug-in connection design, an independent busbar arrangement, and higher-protection options. Rear maintenance access is required.

Explore iPanel-L →

iPanel-E

Simplified, cost-conscious construction with iPanel styling and iDrip monitoring. Wider front-access arrangements can support near-wall installation.

Explore iPanel-E →

AI-iPanel

Compact feeder options, U-section busbars for selected high-current designs, and AI applications. The 500 mm feeder requires 3P devices; drawer circuits are recommended at 400 A or below.

Explore AI-iPanel →

iPanel-M

Shenglong’s medium-voltage platform, with its own construction, ratings, and verification. The low-voltage comparisons above do not apply to iPanel-M.

Explore iPanel-M →

Circuit-Breaker Choice and Project Delivery

All three low-voltage iPanel series can accommodate mainstream circuit-breaker brands, including ABB, Siemens, Schneider Electric, and Shenglong, subject to the selected device dimensions and cabinet arrangement. Shenglong circuit breakers offer a cost-effective project option. For iPanel-L and iPanel-E, 3P or 4P devices do not by themselves impose the AI-iPanel 500 mm-width restriction.

English drawings and operation and maintenance manuals can be provided. Overseas on-site services are quoted separately, with the service scope agreed for the project.

Technical Documentation and Project Support

We support selection and project submissions with configuration information, applicable certification and test documentation, arrangement drawings, and installation requirements. Send your single-line diagram and equipment schedule to begin the review.

Explore Technical Resources →

Plan Your Project with iPanel-E

  • Location, application, quantities, and delivery schedule.
  • Operational voltage, frequency, and earthing system.
  • Main, distribution, and individual circuit current ratings.
  • Short-circuit current, duration, and any internal-arcing requirements.
  • Fixed or withdrawable units, internal separation, and enclosure protection.
  • Local displays, measurements, alarms, protocols, and supervisory interfaces.
  • Cabinet layout, connections, altitude, temperatures, and other site conditions.

If you are still planning your project, send the information you have. We can discuss the remaining details with you.

Prefer email? info@shenglong-hub.com

Ratings and functions apply to their respective configurations. The final equipment, software, documentation, and supply scope are established in the agreed project technical schedule.

← Back to the iPanel Series