SHENGLONG MEDIUM-VOLTAGE SWITCHGEAR
KYN61-40.5 Indoor Metal-Clad Withdrawable Switchgear
Shenglong KYN61-40.5(Z) receives and distributes electrical power in three-phase, 50/60 Hz systems with a rated voltage of 40.5 kV, providing circuit control, protection, and monitoring.
Single-busbar and sectionalised single-busbar arrangements accommodate incoming, outgoing, bus-coupling, isolation, voltage-measurement, and station-service circuits.
We configure electrical ratings, protection, cabinet functions, and connection interfaces around your project requirements.

Product FeaturesTypical ApplicationsTechnical DataCabinet StructureWiring SchemesInstallationService Conditions
Product Features
Metal-Clad Construction
A 2.0 mm aluminium-zinc-coated steel enclosure and metal compartment partitions form a bolted/riveted cabinet, with separate spaces for busbars, the circuit-breaker truck, cables, and low-voltage equipment.
Withdrawable Circuit-Breaker Truck
A screw-driven racking mechanism moves the truck between service and test/isolation positions. Trucks of the same rating and compatible construction are interchangeable.
Automatic Shutters and Interlocking
Shutters cover the fixed contacts when the truck is withdrawn. Mechanical and electrical interlocks coordinate the circuit breaker, truck, earthing switch, and secondary connector.
Insulation and Pressure Relief
Internal air clearances are at least 300 mm. Independent pressure-relief ducts are provided for the main compartments, with the venting route coordinated with the room layout.
Protection and Monitoring
The low-voltage compartment accommodates protection, control, metering, and indication. Optional temperature measurement, partial-discharge monitoring, sequence control, and arc protection are defined in the project scope.
Earthing and Condensation Control
A 6 × 50 mm copper earth bar connects adjacent panels. Heaters and dehumidification equipment help manage humidity, condensation, and corrosion.
Typical Applications
Industrial Power Distribution
Medium-voltage distribution for metallurgy, petrochemical, chemical, paper, cement, textile, automotive, natural-gas, and semiconductor facilities.
Power Plants and Substations
Incoming supplies, feeders, bus sections, isolation, metering, and station-service circuits in power plants, substations, switching stations, and distribution stations.
Infrastructure and Public Facilities
Suitable medium-voltage distribution circuits serving airports, ports, railway facilities, hospitals, commercial complexes, and high-rise buildings.
Renewable Energy Projects
Wind and photovoltaic step-up and collection systems where the equipment voltage, current, and short-circuit duty match the required circuit configuration.
Application suitability is confirmed against the system voltage, load, fault level, operating requirements, and site conditions.
Technical Specifications
| Parameter | Specification |
|---|---|
| Product designation | KYN61-40.5(Z) |
| Equipment type | Indoor metal-clad withdrawable AC switchgear |
| Rated voltage | 40.5 kV |
| Rated frequency | 50 / 60 Hz |
| Rated current | 1250 / 1600 / 2000 / 2500 / 3150 A |
| Main-circuit short-time withstand current | 25 / 31.5 kA for 4 s |
| Main-circuit peak withstand current | 63 / 80 kA, corresponding to the selected withstand class |
| Power-frequency withstand voltage | 95 kV for 1 min, to earth / between phases / across gap |
| Lightning impulse withstand voltage | 185 kV, to earth / between phases / across gap |
| Auxiliary and control circuit withstand voltage | 2000 V for 1 min |
| Enclosure protection | IP3X; IP2X between compartments and with the circuit-breaker compartment door open |
| Internal arc withstand | 31.5 kA for 1 s; applicable tested construction and installation conditions to be confirmed |
| Overall dimensions, W × D × H | 1400 × 2750 / 2800 / 3050 / 3200 × 2600 mm |
| Approximate weight | 1000–2000 kg, depending on scheme |
Cooling and rating selection: 1250–2000 A arrangements use natural cooling with cabinet depths of 2750 / 2800 mm. 2500–3150 A arrangements require forced air cooling, with 31.5 kA / 4 s withstand duty, 80 kA peak withstand, and cabinet depths of 3050 / 3200 mm. Final combinations are confirmed in the project technical schedule.
Cabinet Structure and Equipment
Busbar Compartment
Rounded-corner copper main and branch busbars are supported by partitions and bushings. Heat-shrink sleeving and insulated joint shrouds cover the conductor system.
Circuit-Breaker Compartment
Truck rails, automatic shutters, a screw-driven mechanism, secondary plug, and observation window support defined truck positioning and closed-door operation.
Cable Compartment
Current transformers, the earthing switch, cable terminations, voltage transformers, surge arresters, and the earth bar are selected by circuit duty. A removable bottom cover facilitates cable installation.
Low-Voltage Compartment
Relay protection, control units, instruments, terminals, and indication devices are arranged separately from the high-voltage circuit, with dedicated secondary wiring ducts.
Component and Secondary Interfaces
A ZN85-40.5 vacuum circuit breaker is available, with alternatives agreed for the selected configuration. Typical instrument transformer types include LZZB9-35D current transformers and JDZXP-35 voltage transformers. Ratios, accuracy classes, burdens, and quantities follow the circuit design.
Control supplies are selectable at 110 / 220 V AC or DC. Secondary terminal definitions, spring-charging supplies, interlocks, and communication functions are coordinated with the selected devices.
Primary Wiring Schemes
Schemes 001–030 cover cable incoming/outgoing circuits, bus coupling, isolation, PT, metering, and fuse arrangements. Provide your single-line diagram alongside the required circuit functions.

Primary Wiring Schemes 001–010
Select the image to view the original drawing.

Primary Wiring Schemes 011–020
Select the image to view the original drawing.

Primary Wiring Schemes 021–030
Select the image to view the original drawing.
Typical System Arrangements

Single-Busbar Application Example
Select the image to view the original drawing.

Sectionalised-Busbar Application Example
Select the image to view the original drawing.
These are circuit examples. Component quantities, ratings, protection, and operating sequences are selected for the project.
Dimensions and Installation Planning
| Parameter | Specification |
|---|---|
| Panel width | 1400 mm |
| Panel depth | 2750 / 2800 / 3050 / 3200 mm |
| Panel height | 2600 mm |
| Single-row front operating aisle | At least 3000 mm |
| Rear maintenance aisle | 1500 mm |
| Panel end to wall | 1500 mm |
| Room clear height | At least 4500 mm |
| Face-to-face double-row operating aisle | At least 4000 mm |
Room clearances, access, floor loading, cable trenches, and overhead busbar connections are coordinated in the approved installation drawings. Keep the top pressure-relief route free of cable trays, pipework, and other obstructions.

Switchroom Layout
Select the image to view the original drawing.

Switchroom Section
Select the image to view the original drawing.

Foundation and Base-Plate Openings
Select the image to view the original drawing.
Foundation and Cable Interfaces
An 8# channel-steel foundation frame is used, with its top 15–20 mm above the finished floor. Frame level error is limited to 1 mm/m. Separate power and control cable trenches are provided; the control trench is 250 × 250 mm with a 5 mm checkered-steel cover.
Base-plate interfaces include a front-left secondary cable opening of 300 × 150 mm, a primary cable opening of 650 × 1000 mm, and 8-M8 anchor fixing. Confirm every opening and fixing position against the approved cabinet and civil drawings before construction.
Quality Assurance and Project Documentation
Product engineering references GB/T 3906-2020, GB/T 11022-2020, DL/T 404-2018, and IEC 62271-200. Applicable standards and editions are agreed for the proposed equipment.
We provide technical specifications, cabinet arrangement drawings, installation information, primary and secondary wiring diagrams, and applicable test documentation for project review. Certificates of conformity and factory test reports are supplied according to the agreed documentation scope.
Internal-arc withstand and short-time withstand are different duties. We confirm the applicable tested construction, ratings, and installation conditions for your specification.
Service Conditions
| Parameter | Specification |
|---|---|
| Installation | Indoor, dry, clean, and well ventilated |
| Ambient temperature | −10°C to +40°C |
| 24-hour average temperature | Not more than +35°C |
| Relative humidity | Daily average ≤95%; monthly average ≤90% |
| Normal service altitude | Up to 1000 m |
| Seismic intensity | Not more than intensity 8 |
| Environment | Free from fire and explosion hazards, heavy pollution, chemical corrosion, and severe vibration |
For high altitude, salt fog, elevated humidity, or other special conditions, we review insulation, thermal performance, condensation control, and any required derating with you.
Project Configuration and Enquiry
Send your single-line diagram, equipment schedule, and room layout so we can review circuit functions, current ratings, cooling, protection, cable interfaces, and installation requirements.
Discuss Your KYN61-40.5 Project
- Project location, application, quantities, and delivery schedule.
- System voltage, frequency, current, short-circuit duty, and duration.
- Incoming, outgoing, bus-coupling, PT, metering, and station-service circuits.
- Circuit-breaker, protection, metering, and auxiliary supply requirements.
- Cabinet arrangement, cable specifications, busbar bridges, and site interfaces.
- Forced cooling for 2500 A and above, monitoring, interlocks, and accessories.
- Altitude, temperature, humidity, and other special service conditions.
- Required test documents, drawings, and submission requirements.
If you are still planning your project, send the information you have. We can discuss the remaining details with you.
Prefer email? info@shenglong-hub.com