SHENGLONG MEDIUM-VOLTAGE SWITCHGEAR
KYN28A-24 Indoor Metal-Clad Withdrawable Switchgear
Shenglong KYN28A-24 switchgear provides power distribution, circuit control, protection, and monitoring for medium-voltage installations with a rated voltage of 24 kV and a frequency of 50 or 60 Hz.
A mid-mounted withdrawable truck and separate metal-enclosed compartments accommodate the busbars, circuit breaker, cables, and low-voltage control equipment. We configure incoming, outgoing, bus-coupling, isolation, metering, and voltage-transformer circuits to suit your project.
Front operation and maintenance support compact switchroom arrangements, including wall-mounted and back-to-back layouts where the selected configuration permits.

Product FeaturesTypical ApplicationsTechnical SpecificationsCabinet Structure and Functional CompartmentsPrimary Wiring SchemesCabinet Dimensions and Installation LayoutService Conditions
Product Features
Metal-Clad Construction
Aluminium-zinc-coated steel panels and metal partitions separate the functional compartments. CNC-machined, folded panels form the assembled cabinet.
Withdrawable Truck System
Circuit-breaker, voltage-transformer, metering, and isolation trucks are selected by circuit duty. Defined service and test/isolation positions support controlled operation and maintenance.
Automatic Safety Shutters
Metal shutters open and close with truck movement to shield the stationary contacts. Position interlocks coordinate truck movement, circuit-breaker operation, and the earthing switch.
24 kV Insulation Design
The insulation arrangement provides phase-to-phase clearance of at least 180 mm, phase-to-earth clearance of at least 200 mm, and insulator creepage distance of at least 480 mm for the specified service environment.
Dedicated Pressure Relief
Pressure-relief arrangements are provided for the main compartments. Venting paths and the required clear zones are coordinated with the switchroom design.
Protection and Monitoring
Protection relays, metering, indication, and secondary wiring are arranged in the low-voltage compartment. Optional temperature measurement, partial-discharge monitoring, and arc protection are selected according to project requirements.
Typical Applications
KYN28A-24 switchgear can be configured for the following medium-voltage distribution applications.
Industrial Power Distribution
Medium-voltage distribution for manufacturing plants, metallurgical facilities, petroleum and chemical facilities, cement plants, and other industrial installations.
Substations and Distribution Stations
Incoming and outgoing feeders, bus coupling, metering, voltage-transformer, and station-service circuits arranged around the project single-line diagram.
Commercial and Public Buildings
Medium-voltage power distribution for commercial complexes, high-rise buildings, hospitals, and other public facilities.
Transport Infrastructure
Medium-voltage distribution systems serving airports, ports, railway facilities, and urban rail projects. Dedicated traction equipment requirements are reviewed separately.
Renewable Energy Projects
Collection and distribution circuits in wind and photovoltaic projects where the required equipment voltage, current, and short-circuit duty match the selected switchgear configuration.
Project Engineering
We coordinate cabinet functions, protection and metering, cable or busbar connections, room layout, and installation interfaces for the proposed application.
Select the 24 kV equipment class to match the system voltage and insulation requirements. Suitability also depends on the circuit arrangement, rated current, short-circuit duty, service environment, and installation conditions.
Technical Specifications
Electrical ratings are selected together with the circuit arrangement, installed components, and service conditions.
| Parameter | Specification |
|---|---|
| Rated voltage | 24 kV |
| Rated frequency | 50 / 60 Hz |
| Rated current | 630 / 1250 / 1600 / 2000 / 2500 A |
| Main-circuit short-time withstand current | 25 / 31.5 kA for 4 s |
| Main-circuit peak withstand current | 63 / 80 kA, corresponding to the selected withstand class |
| Power-frequency withstand voltage, 1 min | 65 kV to earth and between phases; 79 kV across the interrupter |
| Lightning impulse withstand voltage | 125 kV to earth and between phases; 145 kV across the interrupter |
| Auxiliary and control circuit withstand voltage | 2000 V for 1 min |
| Enclosure protection | IP4X; IP2X between compartments and with the circuit-breaker compartment door open |
| Loss of service continuity / partition class | LSC2B-PM |
| Internal arc classification | IAC AFLR; arc current and duration confirmed for the selected tested configuration |
| Overall dimensions, W × D × H | 1000 × 1800 × 2300 mm |
| Approximate weight | 1000–1500 kg, depending on circuit scheme |
Typical Rating Combinations
| Rated current | Short-time withstand | Peak withstand |
|---|---|---|
| 630–1250 A | 25 kA / 4 s | 63 kA |
| 1600–2500 A | 31.5 kA / 4 s | 80 kA |
Cabinet Structure and Functional Compartments
Busbar Compartment
Rectangular copper main and branch busbars use insulated supports, heat-shrink sleeving, and joint covers. Busbar sections and connections are selected by current rating.
Circuit-Breaker Compartment
Truck guides, shutters, the racking mechanism, secondary connector, and observation window support truck positioning and closed-door operation.
Cable Compartment
The cable compartment accommodates current transformers, the earthing switch, cable terminations, and optional voltage transformers or surge arresters. Cable fixing height is at least 700 mm.
Low-Voltage Compartment
Protection and control equipment, instruments, terminal blocks, and secondary wiring are arranged separately from the high-voltage circuits. Control wiring runs through screened metal trunking.
Interlocking and Earthing
Mechanical and electrical interlocks coordinate the circuit breaker, truck, earthing switch, and secondary plug. Optional padlocks, electromagnetic locks, and shutter locking devices provide additional access and operating control.
A copper earth bar connects adjacent cubicles and provides connection points for equipment earthing. Anti-condensation heaters are provided to help manage humidity and temperature variation.
Primary Wiring Schemes
The following primary circuit diagrams cover schemes 1–25. We select and adapt the circuit arrangement to your single-line diagram, including incoming and outgoing feeders, isolation, bus coupling, voltage transformers, metering, and station-transformer circuits.

Primary Wiring Schemes 1–5

Primary Wiring Schemes 6–10

Primary Wiring Schemes 11–15

Primary Wiring Schemes 16–20

Primary Wiring Schemes 21–25
Identify both the required circuit function and the single-line diagram in your enquiry. Scheme numbers refer to this KYN28A-24 scheme set.
Cabinet Dimensions and Installation Layout
| Parameter | Specification |
|---|---|
| Width | 1000 mm |
| Depth | 1800 mm |
| Height | 2300 mm |
| Single-row front operating aisle | Minimum 1.5 m; 2.0 m recommended |
| Face-to-face double-row operating aisle | Minimum 2.0 m |
| Bottom cable trench depth | At least 800 mm |
Bottom cable entry and overhead or busbar-bridge connections are configured for the project. Final access clearances, floor loading, cable openings, and pressure-relief zones are coordinated with the approved installation design.
The foundation uses a No. 10 channel-steel base frame with No. 5 channel-steel cross braces. The base frame outline is 1740 × 1000 mm for a 1000 mm-wide cabinet. Elevated-floor installations require coordinated opening dimensions and structural load verification.
Secondary Interfaces and Options
| Parameter | Specification |
|---|---|
| Control supply | 110 / 220 V AC or DC, according to the selected equipment |
| Truck secondary interface | 58-pin connector; connection and disconnection in test/isolation position |
| Instrument transformers | Current and voltage transformer ratios, accuracy classes, and burdens selected by circuit requirements |
| Optional equipment | Truck transfer trolley, busbar bridge, surge arresters, zero-sequence CT, live indication, electromagnetic locking, arc protection, and heater controller |
We define the selected accessories, monitoring functions, and auxiliary supplies in the project scope.
Standards and Technical Support
Product engineering references GB/T 3906-2020, GB/T 11022-2020, DL/T 404-2018, and IEC 62271-200. Applicable standards and editions are agreed for the proposed equipment.
We support product selection and project submissions with technical data, primary and secondary wiring diagrams, arrangement drawings, installation information, and applicable test documentation. Product certificates and factory test reports are supplied according to the agreed project requirements.
Service Conditions
| Parameter | Specification |
|---|---|
| Installation | Indoor |
| Ambient temperature | −15°C to +40°C |
| 24-hour average temperature | Not more than +35°C |
| Relative humidity | Daily average ≤95%; monthly average ≤90% |
| Normal service altitude | Up to 1000 m |
| Seismic intensity | Not exceeding intensity 8 |
| Environment | Free from fire and explosion hazards, heavy pollution, chemical corrosion, and severe vibration |
For higher altitudes, salt fog, high humidity, or other special conditions, we review insulation, temperature-rise, enclosure, and derating requirements for the site.
Project Configuration and Enquiry
- Project location, site conditions, quantities, and delivery schedule.
- System voltage, frequency, required current, and short-circuit duty.
- Single-line diagram, circuit schedule, and cabinet arrangement.
- Protection, metering, instrument transformer, and control supply requirements.
- Cable entry, busbar bridges, switchroom layout, and foundation interfaces.
- Monitoring, interlocks, accessories, and required technical documents.
Discuss Your KYN28A-24 Switchgear Project
Send us your electrical specifications and single-line diagram. We can review suitable cabinet configurations, circuit arrangements, installation interfaces, and supporting documentation for your application.
If you are still planning your project, send the information you have. We can discuss the remaining details with you.