KYN28A-24 Medium-Voltage Switchgear

SHENGLONG MEDIUM-VOLTAGE SWITCHGEAR

KYN28A-24 Indoor Metal-Clad Withdrawable Switchgear

Shenglong KYN28A-24 switchgear provides power distribution, circuit control, protection, and monitoring for medium-voltage installations with a rated voltage of 24 kV and a frequency of 50 or 60 Hz.

A mid-mounted withdrawable truck and separate metal-enclosed compartments accommodate the busbars, circuit breaker, cables, and low-voltage control equipment. We configure incoming, outgoing, bus-coupling, isolation, metering, and voltage-transformer circuits to suit your project.

Front operation and maintenance support compact switchroom arrangements, including wall-mounted and back-to-back layouts where the selected configuration permits.

Discuss Your ProjectTechnical Specifications

KYN28A-24 switchgear cabinet lineup
KYN28A-24 Medium-Voltage Switchgear

Product FeaturesTypical ApplicationsTechnical SpecificationsCabinet Structure and Functional CompartmentsPrimary Wiring SchemesCabinet Dimensions and Installation LayoutService Conditions

Product Features

Metal-Clad Construction

Aluminium-zinc-coated steel panels and metal partitions separate the functional compartments. CNC-machined, folded panels form the assembled cabinet.

Withdrawable Truck System

Circuit-breaker, voltage-transformer, metering, and isolation trucks are selected by circuit duty. Defined service and test/isolation positions support controlled operation and maintenance.

Automatic Safety Shutters

Metal shutters open and close with truck movement to shield the stationary contacts. Position interlocks coordinate truck movement, circuit-breaker operation, and the earthing switch.

24 kV Insulation Design

The insulation arrangement provides phase-to-phase clearance of at least 180 mm, phase-to-earth clearance of at least 200 mm, and insulator creepage distance of at least 480 mm for the specified service environment.

Dedicated Pressure Relief

Pressure-relief arrangements are provided for the main compartments. Venting paths and the required clear zones are coordinated with the switchroom design.

Protection and Monitoring

Protection relays, metering, indication, and secondary wiring are arranged in the low-voltage compartment. Optional temperature measurement, partial-discharge monitoring, and arc protection are selected according to project requirements.

Typical Applications

KYN28A-24 switchgear can be configured for the following medium-voltage distribution applications.

Industrial Power Distribution

Medium-voltage distribution for manufacturing plants, metallurgical facilities, petroleum and chemical facilities, cement plants, and other industrial installations.

Substations and Distribution Stations

Incoming and outgoing feeders, bus coupling, metering, voltage-transformer, and station-service circuits arranged around the project single-line diagram.

Commercial and Public Buildings

Medium-voltage power distribution for commercial complexes, high-rise buildings, hospitals, and other public facilities.

Transport Infrastructure

Medium-voltage distribution systems serving airports, ports, railway facilities, and urban rail projects. Dedicated traction equipment requirements are reviewed separately.

Renewable Energy Projects

Collection and distribution circuits in wind and photovoltaic projects where the required equipment voltage, current, and short-circuit duty match the selected switchgear configuration.

Project Engineering

We coordinate cabinet functions, protection and metering, cable or busbar connections, room layout, and installation interfaces for the proposed application.

Select the 24 kV equipment class to match the system voltage and insulation requirements. Suitability also depends on the circuit arrangement, rated current, short-circuit duty, service environment, and installation conditions.

Technical Specifications

Electrical ratings are selected together with the circuit arrangement, installed components, and service conditions.

Parameter Specification
Rated voltage 24 kV
Rated frequency 50 / 60 Hz
Rated current 630 / 1250 / 1600 / 2000 / 2500 A
Main-circuit short-time withstand current 25 / 31.5 kA for 4 s
Main-circuit peak withstand current 63 / 80 kA, corresponding to the selected withstand class
Power-frequency withstand voltage, 1 min 65 kV to earth and between phases; 79 kV across the interrupter
Lightning impulse withstand voltage 125 kV to earth and between phases; 145 kV across the interrupter
Auxiliary and control circuit withstand voltage 2000 V for 1 min
Enclosure protection IP4X; IP2X between compartments and with the circuit-breaker compartment door open
Loss of service continuity / partition class LSC2B-PM
Internal arc classification IAC AFLR; arc current and duration confirmed for the selected tested configuration
Overall dimensions, W × D × H 1000 × 1800 × 2300 mm
Approximate weight 1000–1500 kg, depending on circuit scheme
Rating selection: The standard selection range above is separate from the 40 kA tested configuration. Projects requiring 40 kA are reviewed individually for the applicable equipment construction, circuit-breaker rating, and supporting documentation.

Typical Rating Combinations

Rated current Short-time withstand Peak withstand
630–1250 A 25 kA / 4 s 63 kA
1600–2500 A 31.5 kA / 4 s 80 kA

Cabinet Structure and Functional Compartments

KYN28A-24 compartment cross-section and component legend

Cabinet Construction

Busbar Compartment

Rectangular copper main and branch busbars use insulated supports, heat-shrink sleeving, and joint covers. Busbar sections and connections are selected by current rating.

Circuit-Breaker Compartment

Truck guides, shutters, the racking mechanism, secondary connector, and observation window support truck positioning and closed-door operation.

Cable Compartment

The cable compartment accommodates current transformers, the earthing switch, cable terminations, and optional voltage transformers or surge arresters. Cable fixing height is at least 700 mm.

Low-Voltage Compartment

Protection and control equipment, instruments, terminal blocks, and secondary wiring are arranged separately from the high-voltage circuits. Control wiring runs through screened metal trunking.

Interlocking and Earthing

Mechanical and electrical interlocks coordinate the circuit breaker, truck, earthing switch, and secondary plug. Optional padlocks, electromagnetic locks, and shutter locking devices provide additional access and operating control.

A copper earth bar connects adjacent cubicles and provides connection points for equipment earthing. Anti-condensation heaters are provided to help manage humidity and temperature variation.

Primary Wiring Schemes

The following primary circuit diagrams cover schemes 1–25. We select and adapt the circuit arrangement to your single-line diagram, including incoming and outgoing feeders, isolation, bus coupling, voltage transformers, metering, and station-transformer circuits.

KYN28A-24 primary wiring schemes 1 to 5

Primary Wiring Schemes 1–5

KYN28A-24 primary wiring schemes 6 to 10

Primary Wiring Schemes 6–10

KYN28A-24 primary wiring schemes 11 to 15

Primary Wiring Schemes 11–15

KYN28A-24 primary wiring schemes 16 to 20

Primary Wiring Schemes 16–20

KYN28A-24 primary wiring schemes 21 to 25

Primary Wiring Schemes 21–25

Identify both the required circuit function and the single-line diagram in your enquiry. Scheme numbers refer to this KYN28A-24 scheme set.

Cabinet Dimensions and Installation Layout

Parameter Specification
Width 1000 mm
Depth 1800 mm
Height 2300 mm
Single-row front operating aisle Minimum 1.5 m; 2.0 m recommended
Face-to-face double-row operating aisle Minimum 2.0 m
Bottom cable trench depth At least 800 mm

Bottom cable entry and overhead or busbar-bridge connections are configured for the project. Final access clearances, floor loading, cable openings, and pressure-relief zones are coordinated with the approved installation design.

KYN28A-24 installation and foundation drawing

Installation and Foundation

KYN28A-24 floor openings and elevated floor installation drawings

Floor Openings and Elevated Floors

The foundation uses a No. 10 channel-steel base frame with No. 5 channel-steel cross braces. The base frame outline is 1740 × 1000 mm for a 1000 mm-wide cabinet. Elevated-floor installations require coordinated opening dimensions and structural load verification.

Secondary Interfaces and Options

Parameter Specification
Control supply 110 / 220 V AC or DC, according to the selected equipment
Truck secondary interface 58-pin connector; connection and disconnection in test/isolation position
Instrument transformers Current and voltage transformer ratios, accuracy classes, and burdens selected by circuit requirements
Optional equipment Truck transfer trolley, busbar bridge, surge arresters, zero-sequence CT, live indication, electromagnetic locking, arc protection, and heater controller

We define the selected accessories, monitoring functions, and auxiliary supplies in the project scope.

Standards and Technical Support

Product engineering references GB/T 3906-2020, GB/T 11022-2020, DL/T 404-2018, and IEC 62271-200. Applicable standards and editions are agreed for the proposed equipment.

We support product selection and project submissions with technical data, primary and secondary wiring diagrams, arrangement drawings, installation information, and applicable test documentation. Product certificates and factory test reports are supplied according to the agreed project requirements.

Service Conditions

Parameter Specification
Installation Indoor
Ambient temperature −15°C to +40°C
24-hour average temperature Not more than +35°C
Relative humidity Daily average ≤95%; monthly average ≤90%
Normal service altitude Up to 1000 m
Seismic intensity Not exceeding intensity 8
Environment Free from fire and explosion hazards, heavy pollution, chemical corrosion, and severe vibration

For higher altitudes, salt fog, high humidity, or other special conditions, we review insulation, temperature-rise, enclosure, and derating requirements for the site.

Project Configuration and Enquiry

  • Project location, site conditions, quantities, and delivery schedule.
  • System voltage, frequency, required current, and short-circuit duty.
  • Single-line diagram, circuit schedule, and cabinet arrangement.
  • Protection, metering, instrument transformer, and control supply requirements.
  • Cable entry, busbar bridges, switchroom layout, and foundation interfaces.
  • Monitoring, interlocks, accessories, and required technical documents.

Discuss Your KYN28A-24 Switchgear Project

Send us your electrical specifications and single-line diagram. We can review suitable cabinet configurations, circuit arrangements, installation interfaces, and supporting documentation for your application.

If you are still planning your project, send the information you have. We can discuss the remaining details with you.

Prefer email? info@shenglong-hub.com

Technical specifications and configuration options are subject to the approved project technical agreement and final manufacturer confirmation. Test documentation applies to its respective tested construction and rated range.