GGD Low-Voltage Distribution Switchgear

Low-Voltage Power Distribution and Control

Shenglong’s GGD low-voltage AC distribution equipment is used for electrical power conversion, distribution, and control of power, lighting, and associated distribution circuits.

The product manual describes applications in power plants, substations, and industrial facilities. Cabinet functions, switching devices, protection, metering, and electrical ratings are selected according to project requirements.

Product Features

Assembled Cabinet Construction

The manual describes an assembled C-section steel frame with removable hinge arrangements. Cabinet construction and electrical layouts are selected to suit the required functions and equipment.

Front and Rear Access

The manual describes single front doors for 600 and 800 mm-wide cabinets, and symmetrical double front doors for 1000 and 1200 mm-wide cabinets. The rear uses a double-door arrangement.

The described cabinet requires rear access and is intended for installation away from the wall. Confirm operating and maintenance clearances against the project drawings.

Removable Top Cover

The cabinet top cover can be removed when required for main busbar assembly and adjustment, as described in the manual.

Configurable Cabinet Functions

The manual lists incoming, bus-coupler, feeder, motor control, reactive power compensation, and lighting distribution cabinets. Specify the required circuit arrangement, components, protection, and metering during technical design.

Catalogue Specifications

The following values are taken from the supplied June 2026 edition of the GGD manual. They describe the catalogue series and should be distinguished from the separately documented high-current configuration below.

Parameter Catalogue Information
Product designation GGD
Operational voltage 380 / 400 V AC in the manual overview; the model table lists 380 V AC
Frequency options 50 / 60 Hz in the manual overview; confirm the selected configuration
Rated insulation voltage 660 V AC in the catalogue model table
GGD1 current options 400 / 600 (630) / 1000 A
GGD2 current options 1000 / 1500 (1600) A
GGD3 current options 2000 / 2500 / 3150 A

These values are catalogue data. Confirm the complete assembly rating, protective device selection, short-circuit capability, and applicable supporting documentation for the proposed equipment.

Documented High-Current Configuration

The supplied type test report 03401-24-04079C-S separately covers GGD equipment with main busbar rated currents of 4000–6300 A. The report identifies Shenglong Electric Group Co., Ltd. as the producer and manufacturing enterprise.

The following information comes from the report’s scope page and applies to the configurations described in that document.

Parameter Report Scope
Product designation GGD
Rated voltage options 380 / 400 / 415 / 440 / 460 / 480 / 500 / 525 / 660 / 690 V AC
Rated insulation voltage 1000 V
Rated frequency 50 Hz
Main busbar rated current 4000–6300 A
Main busbar rated short-time withstand current 100 kA; confirm the required duration against the detailed report
Installation Indoor
Enclosure protection within the stated scope IP30 / IP31 / IP32 / IP40 / IP41 / IP42 / IP43

The report identifies the submitted representative sample as 6300 A, 690 V, 50 Hz, with a rated insulation voltage of 1000 V and IP43 enclosure protection.

These report values must not be applied automatically to GGD1, GGD2, GGD3, or other cabinet arrangements. Confirm the proposed equipment’s construction, components, voltage, current, and short-circuit requirements against the report scope.

Test Documentation

Report 03401-24-04079C-S was issued by Hunan Electric Research Institute Testing Group Co., Ltd. It references GB/T 7251.2-2023 and records a conforming overall conclusion, with completion dated 28 April 2024.

The reviewed summary records passing results for items including:

  • Mechanical operation and enclosure protection.
  • Clearances and creepage distances.
  • Protection against electric shock and integrity of protective circuits.
  • Internal circuits, connections, and external conductor terminals.
  • Dielectric properties.
  • Temperature-rise limits.
  • Short-circuit withstand strength.

Other summary items, including mechanical impact protection and electromagnetic compatibility, are marked as not applicable or not tested. This report does not establish an IK rating or an EMC test pass for the series.

Results apply to the equipment and conditions described in the report. Request the applicable documentation for the configuration proposed for your project.

Cabinet Layout and Installation

Confirm cabinet dimensions, incoming and outgoing circuit arrangements, busbar connections, cable entry, access space, and installation clearances using project drawings.

Identify connections to transformers, adjacent switchboards, and busduct systems during technical design. Cabinet width options do not establish the final depth, height, or dimensions of a high-current configuration.

Service Conditions

The product manual describes the following normal operating conditions:

  • Ambient air temperature: −5°C to +40°C.
  • Average ambient temperature over 24 hours: no more than +35°C.
  • Installation altitude: no more than 2000 m.
  • Relative humidity: no more than 50% at +40°C; higher humidity is permitted at lower temperatures, with 90% at +20°C given as an example.
  • Locations without severe vibration, impact, or conditions that would cause corrosion of electrical components.

Consider condensation caused by temperature changes. For conditions outside the stated limits, confirm suitable protective measures, derating, or a customised configuration with the manufacturer.

Discuss Your Project

Please provide the project location, operational voltage and frequency, required assembly and circuit currents, short-circuit current and duration, earthing system, and a single-line diagram if available.

Include requirements for incoming and outgoing circuits, bus coupling, motor control, reactive power compensation, lighting distribution, protection and metering, enclosure protection, cable access, cabinet layout, and site conditions.

Identify harmonic-producing loads and any required busbar connections to transformers or other switchboards.

Contact us at info@shenglong-hub.com to request product documentation and discuss a suitable GGD configuration.