Withdrawable Power Distribution and Motor Control
Shenglong’s GCK1 low-voltage withdrawable switchgear provides incoming power distribution, outgoing feeders, bus coupling, lighting distribution, and motor control in 380 V AC, 50 Hz systems.
The supplied manual describes power centre (PC) and motor control centre (MCC) arrangements, with fixed and withdrawable sections combined where required. Components, circuit arrangements, protection, and control functions are selected for the project.
Product Features
Modular Assembled Frame
The cabinet uses a bolted frame assembled from dedicated sections. The manual specifies a basic construction module of E = 20 mm for frame components and mounting positions.
Standardised components support different cabinet functions and functional-unit arrangements.
Separate Functional Areas
The MCC arrangement described in the manual separates the horizontal busbars, vertical busbars, functional units, cables, and neutral/protective conductors into dedicated areas.
Confirm the required internal separation, cable space, and access arrangements for the proposed equipment.
Withdrawable Drawer Units
Drawer units use a lever-operated insertion and withdrawal arrangement. The manual describes single-lever operation for units up to 320 mm high and upper and lower levers for units 400 mm high and above.
Secondary connectors use a guided arrangement to support alignment. Interchangeability must be confirmed for units with matching functions and compatible specifications.
Protection and Control
The manual describes incoming protection and motor control functions selected to suit the circuit. Specify short-circuit, overload, undervoltage, control, indication, and source-changeover requirements during technical design.
Functions depend on the installed switching devices, protection equipment, and control scheme.
Technical Specifications
The following values are catalogue data from the supplied GCK1 manual. Confirm the ratings and supporting documentation for the equipment currently offered.
| Parameter | Catalogue Specification |
|---|---|
| Product designation | GCK1 |
| Equipment type | Indoor low-voltage withdrawable switchgear |
| Rated operational voltage | 380 V AC |
| Rated frequency | 50 Hz |
| Rated insulation voltage | 660 V |
| Horizontal busbar current options | 1600 / 2000 / 3150 A |
| Vertical busbar current options | 630 / 800 A |
| Main-circuit plug-in contact current options | 200 / 400 / 630 A |
| Auxiliary-circuit plug-in contact current options | 10 / 20 A |
| Enclosure protection | IP40, as listed in the manual |
| Basic construction module | 20 mm |
Busbar and plug-in contact ratings are separate from the continuous current rating of an individual circuit. Confirm circuit loading, component selection, temperature rise, and any necessary derating for the selected assembly.
Specify the required short-circuit current and duration during the technical enquiry. Confirm the assembly withstand capability and protective device breaking capacity separately against the applicable technical documents.
Drawer Sizes
The manual lists eight standard MCC drawer heights. The required size depends on the circuit equipment, wiring, and thermal requirements.
| Drawer Code | Height |
|---|---|
| A | 160 mm |
| B | 240 mm |
| C | 320 mm |
| D | 400 mm |
| E | 480 mm |
| F | 560 mm |
| G | 640 mm |
| H | 720 mm |
Codes A–H identify drawer sizes; they are separate from the basic construction module E = 20 mm. The manual gives drawer-unit dimensions of 510 mm wide by the selected height by 360 mm deep.
Confirm the number and combination of drawers against the approved cabinet layout. No maximum drawer quantity is specified here.
Cabinet Dimensions
The manual describes the following cabinet dimensions. Width, depth, and height are listed in that order.
| Cabinet Arrangement | Catalogue Dimensions |
|---|---|
| PC cabinet | 600 / 800 / 1000 mm wide × 1000 mm deep × 2200 mm high, depending on equipment |
| MCC cabinet | 600 × 1000 × 2200 mm or 600 × 800 × 2200 mm |
| Rear-door MCC arrangement | 800 × 500 × 2200 mm |
Dimensions are catalogue references. Confirm the final cabinet lineup, component arrangement, cable entry, busbar connections, operating space, and maintenance access against the project drawings.
Cabinet Functions
Power Distribution
PC arrangements accommodate incoming supplies, bus coupling, and outgoing distribution circuits. Provide the single-line diagram, required current ratings, protection scheme, and connection requirements.
Motor Control
The manual illustrates non-reversing, reversing, star-delta, and two-speed motor control circuits. Specify the motor ratings, starting methods, duty, control voltage, and protection requirements.
Power Factor Compensation
The supplied manual also describes GCJ1 power factor compensation arrangements within the related product family. Where compensation is required, confirm the applicable cabinet designation, capacity, switching steps, and harmonic conditions separately.
Service Conditions
The manual describes the following operating conditions:
- Indoor installation at an altitude no higher than 2000 m.
- Ambient air temperature: −5°C to +40°C.
- Average ambient temperature over 24 hours: no more than +35°C.
- Relative humidity: no more than 50% at +40°C; higher humidity is permitted at lower temperatures, with 90% at +20°C given as an example.
- Locations without fire or explosion hazards, severe dust, severe vibration, or exposure to rain.
For conditions outside these limits, agree suitable measures with the manufacturer before specifying the equipment.
Technical Documentation
This overview is based on the supplied GCK1/GCL1 product manual. Catalogue information does not replace configuration-specific verification or certification documents.
The manual references historical standards, including IEC 439 and ZBK 36001-89. Confirm the standards, editions, component availability, and supporting documentation applicable to the equipment currently offered.
The use of a particular component brand does not establish that the complete cabinet is an authorised product of that brand.
Discuss Your Project
Please provide the project location, operating voltage and frequency, required assembly and circuit currents, short-circuit current and duration, earthing system, and a single-line diagram if available.
Include requirements for incoming and outgoing circuits, bus coupling, motor starting, protection and metering, drawer arrangements, control power, cable access, cabinet layout, and site conditions.
Contact us at info@shenglong-hub.com to request product documentation and discuss a suitable GCK configuration.