MNS-L Low-Voltage Switchgear

SHENGLONG LOW-VOLTAGE SWITCHGEAR

MNS-L Low-Voltage Switchgear

Shenglong MNS-L provides modular power distribution, centralised motor control, and automatic power factor compensation for 380/400 V, 50 Hz systems.

Independently developed by Shenglong on the basis of the MNS system, MNS-L offers fixed and withdrawable constructions, main busbar ratings up to 6300 A, and enclosure options up to IP54.

We configure incoming supplies, bus coupling, outgoing circuits, drawer units, and protection to suit your project requirements.

Discuss Your ProjectTechnical Specifications

MNS-L low-voltage power distribution and motor-control switchgear lineup
MNS-L switchgear. Cabinet lineups and installed equipment are selected for each project.

Product FeaturesTypical ApplicationsTechnical DataDrawer UnitsCabinet OptionsInstallationService Conditions

Product Features

Modular Cabinet Construction

An assembled C-section steel frame and 25 mm functional height module accommodate different circuit and unit combinations. Detachable hinges support door installation and maintenance.

Segregated Functional Areas

Dedicated spaces accommodate horizontal busbars, equipment, cables, and control circuits. Flame-retardant functional plates separate busbars from equipment; perforated metal partitions separate vertically adjacent drawers.

Interchangeable Drawer Units

Drawers of the same rating and compatible specification share standardised dimensions and corresponding primary and secondary plug-in connections, supporting planned replacement with standby units.

Three-Position Operation

Connected: main and control circuits connected. Test: main circuit disconnected with the control circuit connected. Disconnected: both circuits disconnected, allowing locking or withdrawal.

Busbar and Earthing System

Rectangular copper vertical busbars are embedded in flame-retardant functional plates. Neutral and protective conductors are arranged for the specified TN-S or TN-C system.

Protection and Monitoring Options

Enclosure protection options extend to IP54, with impact resistance up to IK10. Electrical measurements, switching status, intelligent meters, and communication interfaces can be included in the selected configuration.

Typical Applications

Power Plants and Substations

Low-voltage incoming supplies, bus sections, auxiliary distribution, and outgoing circuits in generation and grid installations.

Industrial Facilities

Power distribution and centralised motor control in petroleum, chemical, metallurgical, textile, and other industrial plants.

Commercial Buildings and Data Centres

Low-voltage distribution systems in high-rise buildings, commercial complexes, and data centres, configured for the required load and operating scheme.

Power Factor Correction

Automatic reactive power compensation using selected capacitor stages, controllers, switching equipment, and protective devices.

We review suitability against the system voltage, fault level, circuit duties, service conditions, and required continuity of operation.

Technical Specifications

Parameter Specification
Product designation MNS-L
Construction Fixed and withdrawable low-voltage AC switchgear
Rated operational voltage 380 / 400 V AC
Rated insulation voltage 660 / 690 V, according to configuration
Rated frequency 50 Hz
Main busbar current Up to 6300 A; double-fronted cabinet arrangement: 2000 A
Distribution busbar current 400–6300 A, according to configuration
Main and distribution busbar short-time withstand 80 kA for 1 s
Main and distribution busbar peak withstand 176 kA; specified duration 0.1 s
Power-frequency withstand voltage, 1 min Main circuit: 2500 V; auxiliary circuit: 1760 V
Enclosure protection options IP30 / IP40 / IP41 / IP54
Enclosure impact resistance Up to IK10
Drawer unit current options 125 / 250 / 400 / 630 A, subject to circuit configuration and thermal derating
Basic height module E = 25 mm

Rating selection: Busbar ratings are separate from individual circuit and drawer ratings. Current capacity, enclosure protection, ventilation, component sizes, and temperature rise are coordinated for the selected assembly. Rated insulation voltage is separate from operational voltage.

Withdrawable Functional Units

Drawer dimensions and mechanisms are selected around the circuit current, installed equipment, heat dissipation, and operating needs.

MNS-L withdrawable outgoing cabinet showing drawers and busbar arrangement

Withdrawable Outgoing Cabinet

MNS-L withdrawable functional drawer unit

Withdrawable Functional Unit

Drawer Heights and Combinations

Unit size Functional height
6E 150 mm
8E 200 mm
12E 300 mm
16E 400 mm
24E 600 mm

Small-unit arrangements with distribution adapters support heights of 150, 160, and 200 mm. Different unit sizes can be combined in one cabinet. The final quantity is determined from the available functional space and the approved circuit arrangement.

Thermal derating may require a larger unit height. A component frame rating does not establish the continuous current rating of the complete drawer circuit.

Push-Pull and Crank Mechanisms

MNS-L push-pull and crank drawer mechanism assembly diagrams

Push-Pull and Crank Mechanisms

Push-pull operation uses direct handle movement for small and medium current units. Crank operation uses a screw mechanism to provide controlled engagement for larger units. Both provide three-position positioning and interlocking.

Interlocking and Secondary Connections

Mechanical interlocking is supplemented by electrical interlocking. Three-incoming-supply arrangements can incorporate two-of-three blocking. Secondary plug-in contacts maintain the control circuit connection in connected and test positions.

Cabinet and Functional Options

Power Distribution Centre

Incoming supplies, bus coupling, and feeders with selected circuit breakers, current transformers, metering, and protection.

Motor Control Centre

Selected drawer units integrate circuit breakers, contactors, overload protection, and associated control wiring. Motor ratings, starting methods, and circuit quantities are defined during engineering.

Fixed-Compartment Construction

Fixed-mounted devices occupy individual compartments, with front access for operation and maintenance. Matching fixed and withdrawable cabinets can be combined within one lineup.

Automatic Compensation

Capacitor stages, switching equipment, and controllers are selected for the load. A power factor target of at least 0.9 depends on the compensation design and operating conditions; harmonic mitigation is reviewed where necessary.

MNS-L fixed-compartment functional unit with circuit breaker

Fixed Functional Unit

MNS-L fixed-compartment outgoing cabinet internal structure

Fixed-Compartment Outgoing Cabinet

Dimensions and Installation Planning

Parameter Specification
Standard cabinet width 600 / 800 / 1000 / 1200 mm
Standard cabinet depth 1000 mm; 800 mm optional
Cabinet height 2200 mm
Rear-access compact cabinet 500 mm depth optional; width and arrangement selected by scheme
Cabinet lineup Single row or face-to-face double row, according to layout
Double-fronted cabinets Main busbar current 2000 A

Width and depth combinations are selected by cabinet function. We coordinate cable access, operating and maintenance aisles, foundation fixing, transformer connections, and busbar interfaces in the project arrangement drawings.

Busbar boxes and bridges are specified separately, including rated current, span, and height above the floor. Identify transformer capacity, incoming connection method, and phase sequence during design.

Quality Assurance and Technical Support

Product engineering references GB 7251.1, GB/T 7251.12, IEC 61439-1/-2, and GB 24274. Applicable parts and editions are agreed for the proposed equipment.

Electrical type-test and internal-arcing test documentation is available for applicable MNS-L configurations. We coordinate the supporting documents with your equipment ratings, construction, and project requirements.

Routine inspection includes visual and marking checks, protective-earthing continuity, dielectric testing, mechanical operation, and secondary wiring verification. Certificates of conformity and routine test reports are supplied according to the agreed scope.

Service Conditions

Parameter Specification
Installation Indoor, without fire or explosion hazards, heavy dust, severe vibration, or rain exposure
Ambient temperature −5°C to +40°C
24-hour average temperature Not more than +35°C
Relative humidity Not more than 50% at +40°C; higher humidity permitted at lower temperatures, such as 90% at +20°C
Normal service altitude Up to 2000 m
Earthing arrangements Three-phase four-wire or five-wire, according to the specified system

Condensation is addressed through ventilation, air conditioning, or dehumidification as appropriate. High altitude, salt fog, corrosive environments, elevated humidity, and special temperatures require review of insulation, thermal performance, and protective measures.

Identify large rectifiers and other harmonic-producing loads in your enquiry so that suppression and compensation measures can be reviewed.

Project Configuration and Enquiry

Send your single-line diagram and equipment schedule. We will review busbar ratings, PC and MCC functions, drawer combinations, compensation, cabinet layout, and required supporting documents with you.

Discuss Your MNS-L Project

  • Project location, application, quantities, and delivery schedule.
  • Operational voltage, frequency, earthing system, and required current ratings.
  • Short-circuit current and withstand duration.
  • Incoming, outgoing, bus-coupling, and motor-control circuits.
  • Drawer heights, unit quantities, and fixed or withdrawable arrangements.
  • Protection, metering, compensation, and communication requirements.
  • Enclosure protection, cable access, cabinet layout, and busbar bridges.
  • Harmonic sources, altitude, humidity, temperature, and other site conditions.

If you are still planning your project, send the information you have. We can discuss the remaining details with you.

Prefer email? info@shenglong-hub.com

Technical specifications and configuration options are subject to the approved project technical agreement and final manufacturer confirmation. Test documentation applies to its respective tested constructions and rated ranges.

← Back to Low-Voltage Switchgear