SHENGLONG PREFABRICATED SUBSTATIONS
YB Series Prefabricated Substation
A complete HV/LV power supply unit integrating high-voltage switchgear, a distribution transformer, and low-voltage switchgear within a compartmentalised enclosure.
Shenglong YB substations are available with 12 or 24 kV HV units, a 0.4 kV LV system, and transformer capacities from 630 to 2500 kVA. Factory assembly, internal wiring, and testing simplify site installation.
We configure the supply scheme, transformer, outgoing circuits, enclosure, and monitoring to suit your project.

Product FeaturesTypical ApplicationsTechnical DataConfigurationMonitoringInstallationService Conditions
Product Features
Factory-Assembled Power Supply Unit
The HV unit, transformer, LV unit, and auxiliary systems are assembled and internally wired in the factory. Site work includes positioning, external connections, inspections, and commissioning.
Compartmentalised Construction
Separate HV, transformer, and LV compartments provide dedicated access and equipment space. Triangular, row, and in-line layouts accommodate different capacities and site requirements.
Outdoor Enclosure
IP33D enclosure protection is available as standard, with IP44 optional. Enclosure materials include coated aluzinc steel, aluminium alloy, and cement-based composite panels.
Transformer Cooling
Ventilation louvres and natural convection remove heat, with temperature-controlled fans operating when required. Oil-immersed and dry-type transformers are available.
High-Altitude Configurations
Dedicated configurations have undergone type-test verification at 4500 m. Actual altitude, insulation, cooling, and transformer requirements are reviewed for each high-altitude project.
Integrated Monitoring Options
Optional monitoring terminals provide electrical measurements, equipment status, alarms, and supervisory communication. Additional temperature sensing, video, and access control can be included.
Typical Applications
Urban Distribution
Municipal roads, district distribution installations, street lighting, and landscape lighting supplies.
Residential and Commercial Projects
Residential communities, commercial complexes, industrial parks, schools, and hospitals.
Transport Infrastructure
Expressway service areas, toll stations, interchanges, railway facilities, tunnels, airports, and ports.
Renewable Energy Projects
Wind and photovoltaic auxiliary supplies and suitable step-up applications, with transformer ratio, connection scheme, and protection selected for the project.
Technical Specifications
| Parameter | Specification |
|---|---|
| HV rated voltage | 12 or 24 kV |
| LV rated voltage | 0.4 kV |
| Rated frequency | 50 Hz |
| Transformer capacity options | 630 / 800 / 1000 / 1250 / 1600 / 2000 / 2500 kVA |
| HV busbar rated current | Up to 630 A |
| LV main busbar rated current | Up to 4000 A, matched to transformer capacity and configuration |
| HV short-time withstand | 20 kA for 2 s; peak 50 kA |
| LV main-circuit short-time withstand | 30 kA for 1 s; peak 63 kA |
| Earthing circuit short-time withstand | 17.4 kA for 1 s; peak 43.5 kA |
| Enclosure protection | IP33D; IP44 optional |
| Compartment protection | IP2X and above, according to configuration |
| Roof distributed load capacity | At least 2500 N/m²; additional concentrated loads are not permitted |
Configuration selection: Voltage, transformer capacity, HV and LV current ratings, short-circuit withstand, cooling, and enclosure protection are selected together. Higher fault duties and special operating conditions require project-specific verification.
Insulation Levels
| Circuit | Power-frequency withstand, 1 min | Lightning impulse withstand |
|---|---|---|
| 12 kV HV circuit | 42 kV | 75 kV |
| 24 kV HV circuit | 50 kV | 125 kV |
| LV circuit | 2.5 kV | 7.4 kV |
| Auxiliary and control circuits | 2.0 kV | — |
High-altitude insulation requirements are assessed separately for the actual installation altitude and selected equipment.
Construction and Configuration
High-Voltage Unit
Ring-main, terminal, or dual-source arrangements use switch-fuse or circuit-breaker protection. Cable terminations, separable connectors, manual or motorised operation, and metering are selected by scheme.
Transformer Unit
Sealed oil-immersed or dry-type transformers are available. Vector groups include Dyn11 or Yyn0; impedance options include 4%, 4.5%, or 6%, according to capacity and the selected design.
Low-Voltage Unit
Single-busbar or sectionalised-busbar arrangements provide the required incoming supply, outgoing feeders, metering, protection, and reactive compensation.
Enclosure and Auxiliary Systems
A welded channel-steel base supports the enclosure, with lifting points and foundation fixing. Lighting, temperature/humidity control, and maintenance accessories are specified in the supply scope.
Ventilation and Noise Control
Transformer-room louvres and temperature-controlled fans support cooling. Dry-type transformers can include winding-temperature alarms and trip outputs; oil-immersed transformer protection is selected by type and capacity.
A sound level of 51.4 dB(A) was measured for the corresponding type-tested configuration, against a limit of 55 dB(A). Site noise depends on the selected transformer, cooling, operating conditions, and surroundings. Low-noise transformers, silencers, and acoustic measures can be reviewed for sensitive locations.
Protection, Interlocking, and Earthing
Access and operating interlocks are coordinated with the HV scheme and earthing arrangement. A continuous earth busbar connects the equipment enclosures, doors, and relevant foundation parts; transformer-neutral connections follow the specified system design.
Intelligent Monitoring and System Integration
Measurements and Status
Selected HV/LV electrical values, transformer temperature, compartment temperature and humidity, switch positions, fan status, and door indications.
Alarms and Supervisory Communication
Protection indications, condensation alarms, and selected remote switching functions. Communication interfaces and authorised controls are agreed for the project.
Optional Site Functions
Wireless temperature sensing, video surveillance, access control, and perimeter alarms through the selected equipment and system integration.
Site Layout and Foundation
Overall enclosure dimensions depend on transformer capacity, layout, equipment, and access arrangements. We provide the project arrangement and foundation drawings for civil coordination.
| Parameter | Specification |
|---|---|
| Foundation construction | Reinforced-concrete base and walls, designed for soil conditions and equipment loads |
| Top above finished grade | Generally 300–500 mm, subject to flood-level and site requirements |
| Cable routes | Reserved ducts or trenches with drainage and coordinated cable supports |
| Embedded parts | Continuous channel steel and fixing interfaces coordinated with the enclosure base |
| Installation access | Space for all doors, operation, maintenance, ventilation, and lifting |
The foundation drawing is a schematic. Dimensions, openings, reinforcement, and structural loads follow the approved project drawings. Keep ventilation louvres unobstructed, provide a designed earth grid, and avoid waterlogged locations.
Integral lifting uses the designated base lifting points and the supplied lifting instructions. Inspect level, seating, fixing, earthing, and cable connections before commissioning.
Quality Assurance and Technical Support
Product engineering references GB/T 17467-2020, GB/T 11022-2020, GB/T 7251.8-2020, GB 20052-2020, and GB/T 1094.1-2013. Applicable standards, editions, and transformer energy-efficiency requirements are confirmed for the proposed equipment.
Applicable type-test and certification documents are available for project review. Verification covers the corresponding constructions, including insulation, temperature rise, short-time withstand, enclosure protection, mechanical strength, earthing, and functional tests.
We supply product certificates, factory inspection reports, operating instructions, primary/secondary diagrams, and packing information according to the agreed scope.
Service Conditions
| Parameter | Specification |
|---|---|
| Installation | Outdoor |
| Normal ambient temperature | −25°C to +40°C |
| Cold-region option | Down to −45°C, by specific agreement |
| Normal service altitude | Up to 1000 m |
| High-altitude option | Dedicated configurations verified at 4500 m; actual altitude to be stated |
| Relative humidity | Daily average ≤95%; monthly average ≤90% |
| Environment | Free from fire/explosion hazards, heavy pollution, and chemical corrosion |
| Seismic requirements | Foundation and anchorage designed for local requirements |
State salt fog, sand and dust, heavy condensation, harmonic loads, and unusual temperatures in your enquiry. We coordinate insulation, corrosion protection, filtration, dehumidification, and thermal requirements for the site.
Project Configuration and Enquiry
Discuss Your YB Substation Project
Send your single-line diagram and available site layout. Please include:
- HV/LV voltages, transformer capacity, quantity, and delivery schedule.
- Ring-main, terminal, or dual-source HV supply and required protection.
- LV incomer, feeder circuits, busbar sectioning, compensation, and metering.
- Oil-immersed or dry-type transformer and required efficiency class.
- Enclosure material, colour, protection, dimensions, and access requirements.
- Cable entry/exit mode, sizes, and circuit quantities.
- Site altitude, temperatures, flood level, corrosion, dust, and noise requirements.
- Monitoring, communication, video, access control, and auxiliary functions.
If you are still planning your project, send the information you have. We can discuss the remaining details with you.
Prefer email? info@shenglong-hub.com
Specifications and configurations are subject to the approved project technical agreement and final manufacturer confirmation. Test and certification documents apply to their respective equipment and conditions.