MDmax Low-Voltage Switchgear

Low-Voltage Power Distribution and Control

The supplied MDmax documentation describes low-voltage switchgear assemblies manufactured by Shenglong Electric Group Co., Ltd., including incoming, feeder, and control cabinets.

This overview focuses on the configuration documented in safety type test report 10101-1849872-S. Current equipment availability, component selection, and applicable technical documentation should be confirmed for each project.

Documented Assembly

Incoming, Feeder, and Control Cabinets

The report identifies drawings for incoming, feeder, and control cabinets. Their electrical arrangement and connections should be matched to the required single-line diagram.

Switching and Control Equipment

The tested assembly incorporated ABB air circuit-breakers, moulded-case circuit-breakers, contactors, and overload protection devices, together with other specified components.

These components describe the tested arrangement. Confirm the components currently offered and whether any substitutions affect the applicable verification.

Cooling Arrangement

The report states that the sample used forced-air cooling during the temperature-rise test. Eight fans were installed and all were operating during that test.

The documented 6300 A arrangement must therefore be reviewed together with its cooling system. Confirm ventilation, fan operation, ambient conditions, maintenance access, and any required derating for the proposed installation.

Documented Technical Specifications

The following values are taken from report 10101-1849872-S. They apply to the configurations described in that report and do not establish ratings for every MDmax assembly.

Parameter Documented Specification
Product designation MDmax
Manufacturer Shenglong Electric Group Co., Ltd.
Installation Indoor
Rated operational voltage 400 V AC
Rated insulation voltage 1000 V
Rated frequency 50 Hz
Main busbar rated current 4000–6300 A for the covered configurations
Control cabinet distribution busbar rated current 550–1600 A for the covered configurations
Main busbar rated short-time withstand current 100 kA; confirm the applicable duration from the detailed report
Control cabinet distribution busbar rated short-time withstand current 50 kA; confirm the applicable duration from the detailed report
Enclosure protection IP41
Cooling condition recorded for temperature-rise testing Forced-air cooling with all eight installed fans operating

Busbar ratings are separate from individual outgoing circuit ratings. Confirm the complete combination of voltage, current, short-circuit withstand capability, enclosure protection, cooling, and components for the proposed assembly.

Rated insulation voltage is not the rated operational voltage. The reviewed report lists 400 V AC operation.

Test Documentation

Safety type test report 10101-1849872-S identifies MDmax equipment produced and manufactured by Shenglong Electric Group Co., Ltd. The report references GB 7251.12-2013 and records a conforming conclusion dated 10 October 2014.

The results relate to the sample and construction described in that report. Confirm their applicability to the equipment currently proposed, including any changes to components, cabinet construction, busbars, and cooling.

Request current conformity documentation and any applicable manufacturer authorisation for project review. Historical test documents do not establish current certification status or current brand authorisation.

Project Configuration

Confirm the cabinet functions, incoming and outgoing circuits, switching devices, protection, metering, and control requirements during technical design.

Request drawings showing cabinet dimensions, busbar connections, cable access, operating space, maintenance clearances, and cooling arrangements.

Provide the installation altitude, ambient temperature, humidity, condensation risk, and any unusual environmental conditions so that the proposed configuration can be reviewed.

Discuss Your Project

Please provide the project location, operating voltage and frequency, required assembly and circuit currents, short-circuit current and duration, earthing system, and a single-line diagram if available.

Include requirements for incoming supplies, feeders, motor control, protection and metering, enclosure protection, cooling, cable or busduct connections, and cabinet layout.

Contact us at info@shenglong-hub.com to request product documentation and discuss the required MDmax configuration.